Al-Kadhimiya Diesel Power Station

Daily Generation & Fuel Calculation

Step 1 Report details

Step 2

Generator Meter Readings

Enter today’s cumulative kWh readings. Yesterday’s readings load automatically — the daily difference is calculated for you.

Total Generation Today 0.000 MWh
Step 3

Fuel Meter — Engines 5–8

Monitoring / verification value. The official engine HFO consumption is Total Generation × 0.23 m³/MWh — the meter difference is compared against it, never substituted for it.

Daily meter difference
Step 4

HFO Tank Readings

Quantities are calculated automatically where possible — fields marked calc are derived from pump status, consumption and receipts. Type over a calc value if you have an actual dip reading; clear the field to recalculate. A tank decrease is not automatically consumption.

Leave 0 if no tanker / external delivery was received.

Step 5

HFO Transfer Operations

Fuel Transfer Pump Storage → Settling
Fuel Purifier Settling → Service

Fuel route: Storage → Settling → Service → Engines / Boiler. Internal transfers between tanks are never counted as consumption.

Step 6

HFO Boiler Consumption

MANUAL

Enter 0.000 when the boiler was not operating. Kept separate from engine consumption.

Step 7

D.O. Consumption

ESTIMATED

Estimated operational values — not meter-calculated. The 0.23 HFO factor is never applied to D.O.

Total D.O. (estimated) 0.000 m³